Steady-State Electromagnetic Parameters of 6-Phase Synchronous Generator
Author:
Affiliation:

Fund Project:

  • Article
  • |
  • Figures
  • |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • |
  • Materials
    Abstract:

    Based on the basic principle of Park equation, the basic equation of the 6-phase synchronous generator is established, and d-axis and q-axis equivalent circuits of 6-phase synchronous generator are obtained. Comprehensive mutual reactance in equivalent circuits reflects the magnetic coupling function between double Y of the 6-phase synchronous generator. It consists of armature reaction reactance and comprehensive mutual leakage reactance. Through the analysis of single Y operation (the other Y no-load ) and double Y operation of the 6-phase synchronous generator, it can be obtained that double Y synchronous reactance is equal to the difference of 2 times single Y synchronous reactance and self leakage reactance. Taking the example of no-load short-circuit test, the characteristic curve of 6-phase synchronous generator, the d-axis synchronous reactance, the self leakage reactance, and the short-circuit ratio are measured. The steady-state electromagnetic parameters of the 6-phase synchronous generator are verified with the electromagnetic theory analysis and practical operation characteristics.

    Reference
    Related
    Cited by
Get Citation

GOU Zhide, SUN Yutian, ZHANG Chunli, WEI Yuguo, BEN Xipeng. Steady-State Electromagnetic Parameters of 6-Phase Synchronous Generator[J]. Electric Machines & Control Application,2021,48(3):62-67.

Copy
Share
Article Metrics
  • Abstract:
  • PDF:
  • HTML:
  • Cited by:
History
  • Received:October 29,2020
  • Revised:January 08,2021
  • Adopted:
  • Online: March 20,2021
  • Published: March 10,2021
You are thevisitor
沪ICP备16038578号-3
Electric Machines & Control Application ® 2025
Supported by:Beijing E-Tiller Technology Development Co., Ltd.

沪公网安备 31010702006048号